🔗 ROOF FAN

Specifications & Dimensions

ModelCAPACITY(CMM)DIMENSIONSFANMOTOR
0mmAq5mmAq10mmAq15mmAq20mmAqABCDEFGHIØHPRPM
HRF-303223640640310470401804807006403001/121120
HRF-355441820820360570402005507007003501/81120
HRF-40907968820820410640402206207007504001/41120
HRF-501201119610001000510710502807809508805001/21120
HRF-602342151851501100110061080050340840110090060011120
HRF-7039635733023013451345720980704009201310110070021120
HRF-9060056050042035016301630920105010051011601310120090031120
HRF-12072064058050042020002000122015201005601300120051120

Amount of Ventilations

Table of Required Ventilation Times
work placeNumber of ventilations per hour (times)work placeNumber of ventilations per hour (times)
machine factory10~15coating factory30~60
casting factory30~60woodworking factory15~20
forging factory40~60power station20~30
welding factory15~20substation room30~50
car repair factory10~15boiler room20~60
plating factory15~30office5~10
chemical plant10~30storage6~12
dyeing factory15~30lecture room5~15
paper mill15~30hospital6~12
food factory12~20theater8~20
brewery20~30restaurant8~10
flour mill6~12cuisine20~30
printing factory5~15
spinning factory5~10
How to select the number of models
1) Depending on the conditions of the place requiring ventilation, determine the ventilation times by referring to the ventilation times table.
2) Calculate the volume of the building (㎥) = width (m) x length (m) x height (m).
3) Considering the size of the ventilator, the power condition, etc., the ventilation capacity of each model is calculated from the performance table.
4) Required number = Number of required ventilation X Building volume(㎥) / 60min X Ventilation capacity per unit (㎥/h)